Content |
- PRIORITY CONTROL It controls the priority of emergency, timer, remote1, remote2, main(normal). - AUTO FIRE SENSOR The fire alarm will be given automatically to the designated areas by detecting fire sensor input. - SPEAKER SWITCHING ON EMERGENCY OR NORMAL(MAIN) You can control the speaker relay on emergency or normal(main) mode by using the speaker switch on front panel. - DISPLAY STATUS You can easily check the priority status. - 2 AND 3 WIRE SPEAKER LINE SYSTEM You can control the speaker line on the 2 wire system or 3 wire system. - EXTENSION FUNCTION You can easily expand by connecting additional ECS-616.
ECS-616 | Priority Control | Emergency >Timer > Remote1 > Remote2 > Main | Link in/ out Interface | RS-422(19200bps,Data 8bits,Stop 1bit, Non Parity bit, Start1bit) | Link in/ out interface Distance | 1.2 km | Operation Temperature | -10 °C ~+ 40 °C | Power Source | 24V DC | Power Consumption | 900mA | Weight | 4.8Kg/10.6Ib | Dimensions( W x H x D) | 482(W)x 88(H) x 380(D) mm / 19(W)x 3.5(H)x 15(D)in | ※ Specifications and design subject to change without notice. |
|
The RM-210 is an extension unit for increasing the number of function keys of TOA's RM-200M, RM-200XF and RM-200X Remote Microphones.
Specification |
| Current Consumption | 20mA max. (in terms of RM-200M's DC power input 75mA max. (interms of DC power inputs of RM-200X and RM-200XF) | Connection | Connection to RM-200M, RM-200X or RM-200XF by way of dedicated Cable | Number of Function | Keys 10 | Function | When used to expand the RM-200M:
Selects and activates the Voice Announcement Board messages.
When used to expand the RM-200X and RM-200XF (PC software setting):
Emergency activation, emergency reset, BGM pattern selection, EV message activation, broadcast zone selection, monitor zone selection, chime activation, Talk switch activation, control output activation, input volume adjustment, zone volume adjustment, and failure output indication and reset. | Finish | ABS resin, bluish gray (PANTON 538 or its equivalent) | Dimensions | 110 (W) x 76.5 (H) x 215 (D)mm | Weight | 350g | Accessory | Extension cable x 1, Linkage bracket A x 1, Linkage bracket B x 1, Screw for linkage bracket x 12 |
|
Music Program Selector 1-6 with Relay
Toa - 100V installation |
| - CONVENIENT INSTALLATION AND CONSTRUCTION WITHOUT NEED OF ID SETTING. - SELECTION OF VARIOUS CHIME BROADCASTINGS FOR MIC BROADCASTING (PRE/POST). - CONVENIENT PRIORITY BROADCASTING. - ADOPTION OF OUTPUT SIGNAL LEVEL DISPLAY. - ADOPTION OF RS-422 COMMUNICATION METHOD TO SUPPORT A LONG DISTANCE. | | | | | | Audio Output | 0dB(Balanced) | Audio Input | Paging & RM MIC & LM MIC | -50dB(Balanced) | BGM(Main & Local) | -10dB(Balanced) | Tone Control (100Hz & 10kHz) | Paging MIC | ± 10dB | Audio Output | ± 12dB | Frequency Response | BGM | ± 3dB | MIC | ± 3dB | S / N | BGM | Better than 75dB | MIC | Batter than 65dB | T.H.D. | BGM | Less than 0.05% | MIC | Less than 0.05% | Priority Control | Paging MIC > DRP > RM1> RM2 > RM3 > RM4 > LM-8000 > Main BGM | Phantom Power | DC 24V | Serial Interface | Communication Speed | 9600bps | Communication Distance | Maximum 300m(UTP CAT%) | Operation Temperature | -10℃ ~ +40℃ | Power Source | 100-120VAC or 220-240VAC; 50/60Hz (Supplied AC mains transformer depends on country requirements) | Weight(SET) | 1.5kg / 3.2lb | Dimensions(SET) | 200(W) x 70(H) x 206(D)mm 7.9(W) x 2.8(H) x 8.1(D)in | ※ Specifications and design subject to change without notice. | | | |
|
Emergency combination system. Ενσωματώνεται σε σύστημα συναγερμού φωτιάς. Ενσωματωμένο πυκνωτικό μικρόφωνο για Επείγουσα Αναγγελία, Εξωτερική αυτόματη αναγγελία με αρχείο φωνής, Επιλογέας δοκιμής. Ρύθμιση έντασης εξόδου, Βάρος 4,6kg. Διαστάσεις (WxHxD): 482X88X380mm |
The RM-300MF Fireman's Microphone is designed for exclusive use with the VM-3000 Series. It is equipped with an emergency activation key, permitting pre-recorded evacuation and alert announcements to be activated, and microphone announcement to be made in emergency situations. By connecting the RM-320F Fireman's Microphone Extension to the RM-300MF, the number of function keys can be expanded. The zone selection or failure acknowledgment function can be assigned to such function keys.
Power Source | 24 V DC (operating range: 15 - 40 V DC, supplied from the VM-3000 system) | Current Consumption | 120 mA (RM-300MF), 660 mA (with 3 RM-320F connected) | Frequency Response | 200 Hz - 15 kHz | Distortion | 1 % or less | S/N Ratio | 55 dB or more | Microphone | Unidirectional dynamic microphone with talk key, compressor (on/off switchable) | Volume Control | Microphone volume control, Buzzer volume control | Connection Cable | Main line: Shield CPEV cable (each one pair of Audio line, Data line, Power supply line)
or Category 5 Shielded Twisted-Pair straight cable for LAN (CAT5-STP), M3 screw terminal | Maximum Cable Distance | Total 800 m (874.89 yd) | No. of Connectable RM-320F | Max. 3 units | Operation | Emergency key, Evacuate key, Alert key, Emergency reset key, CPU switch, Reset switch | Indicator | Power indicator, Emergency indicator, Communication failure indicator, CPU OFF indicator,
Evacuation announcement indicator, Alert announcement indicator,
Emergency reset indicator, Microphone in-use indicator,
Emergency broadcast equipment in-use indicator | Operating Temperature | -5 ℃ to +45 ℃ (23 ゜F to 113 ゜F) | Operating Humidity | 5 % to 95 %RH (no condensation) | Finish | ABS resin, blueish gray (PANTONE 538 or its equivalent) | Dimensions | 200 (W) × 215 (H) × 82.5 (D) mm (7.87" × 8.46" × 3.25“) | Weight | 1.1 kg (2.43 lb) (with wall mounting bracket unit) | Accessory | Wall mounting bracket unit …1, Wall mounting screw …2 |
|