Content | A dedicated microphone for the VX-2000 system that fulfills the requirements of British and European standards:BS5839 part 8, EN60849 and IEC60849. The RM-200XF is designed to be exclusively used for emergency broadcast, however it can be used for general purpose broadcast applications as well.
Specification |
|
Power Requirement |
24V DC (Operating range: 16 - 40V DC) |
Current Consumption |
Under 200mA (RM-200XF), 850mA (with 10 RM-210s connected) |
Audio Output |
0db*, 600, balanced |
Hand-Held Microphone |
Dynamic microphone, Function switch (default: Press-talk), Microphone element fault detection |
Distortion |
Under 1% |
Frequency Response |
100 - 15,000Hz |
Signal-to-Noise Ratio |
Over 55dB |
Internal Speaker |
200mW |
Volume Control |
Microphone volume control, Monitor speaker volume control |
Number of Function Keys |
5 (including Hand-held micropnone's switch), extendable up to 105 (with 10 RM-210s connected)
Key Extension 10 keys extension per RM-210, EXTENSION connector |
Number of Connectable Units |
4 |
Communication System |
LONWORKS twisted pair free topology transceiver |
Connection Cable and Connector |
Category 5 STP cable, plug-in screw connector |
Communication Distance |
500m (Free topology wiring) |
Finish |
ABS resin, bluish gray (PANTON 538 or its equivalent) |
Dimensions |
200 (W) x 215 (H) x 82.5 (D)mm (excluding the coiled cord) |
Weight |
1.2kg |
Accessory |
Plug-in screw terminal x 1, Wall mounting bracket x 1, Wall mounting screw x 2, Box mounting screw x 2 |
Applicable Box |
YC-301, YC-11A |
|
*0 dB = 1 V |
| |
Music Program Selector 1-6 with Relay
Toa - 100V installation |
The RM-300MF Fireman's Microphone is designed for exclusive use with the VM-3000 Series. It is equipped with an emergency activation key, permitting pre-recorded evacuation and alert announcements to be activated, and microphone announcement to be made in emergency situations. By connecting the RM-320F Fireman's Microphone Extension to the RM-300MF, the number of function keys can be expanded. The zone selection or failure acknowledgment function can be assigned to such function keys.
Power Source | 24 V DC (operating range: 15 - 40 V DC, supplied from the VM-3000 system) | Current Consumption | 120 mA (RM-300MF), 660 mA (with 3 RM-320F connected) | Frequency Response | 200 Hz - 15 kHz | Distortion | 1 % or less | S/N Ratio | 55 dB or more | Microphone | Unidirectional dynamic microphone with talk key, compressor (on/off switchable) | Volume Control | Microphone volume control, Buzzer volume control | Connection Cable | Main line: Shield CPEV cable (each one pair of Audio line, Data line, Power supply line)
or Category 5 Shielded Twisted-Pair straight cable for LAN (CAT5-STP), M3 screw terminal | Maximum Cable Distance | Total 800 m (874.89 yd) | No. of Connectable RM-320F | Max. 3 units | Operation | Emergency key, Evacuate key, Alert key, Emergency reset key, CPU switch, Reset switch | Indicator | Power indicator, Emergency indicator, Communication failure indicator, CPU OFF indicator,
Evacuation announcement indicator, Alert announcement indicator,
Emergency reset indicator, Microphone in-use indicator,
Emergency broadcast equipment in-use indicator | Operating Temperature | -5 ℃ to +45 ℃ (23 ゜F to 113 ゜F) | Operating Humidity | 5 % to 95 %RH (no condensation) | Finish | ABS resin, blueish gray (PANTONE 538 or its equivalent) | Dimensions | 200 (W) × 215 (H) × 82.5 (D) mm (7.87" × 8.46" × 3.25“) | Weight | 1.1 kg (2.43 lb) (with wall mounting bracket unit) | Accessory | Wall mounting bracket unit …1, Wall mounting screw …2 |
|
RM-200M - Five/ten zone console for VM-2120/2240 amplfiers
The RM-200M Remote Microphone that allows announcements to be made to any speaker zone and emergency announcements to all zones on a system with the VM-2120/2240 system management amplifiers.
These announcements can be made live or pre-recorded announcements
can be activated. The remote microphone is connected by cable to the
RM-210 Remote Microphone Extension unit.
SPECIFICATIONS:
Power Requirement | 24 V DC (12-30 V DC), (Supplied from VM-2120/VM-2240 Amplifier or local power suppy.) | Distortion | Less than 1% | Frequency Response | 100 - 10,000 Hz | Distortion | Less than 1% | Signal-to-Noise Ratio | More than 60 dB | Audio Output | 0 dB*1, 600 O, balanced | Microphone | Unidirectional electret condenser microphone, gooseneck type. | Speaker Zone Control | Zones 1-5 (Zones 1-10 with 2 stacked amplifiers) Groups 1-2, and All-Zone Broadcast | Emergency Broadcast | Activation of Emergency Broadcast (pre-recorded announcement*2 or live microphone announcement) by Emergency Switch | Voice Announcement Board Control | Activation of 5 messages*2 | Number of Connectable Units | Up to 4 | Communication System | RS-485 | Volume Control | Microphone volume control | Connection Cable and Connector Category | 5 STP cable, RJ45 connector | Communication Distance | 800 m maximum in total | Finish | ABS resin | Dimensions | 190 (W) × 75.7 (H) × 21.5 (D) mm (Gooseneck microphone excluded) |
| *1 0 dB = 1 V
*2 An optional EV-200 Board must be mounted in the VM-2120 or VM-2240 Amplifier. |
|
The AT series high quality attenuators features 5 attenuation settings ,,OFF'' -18dB,-12db,-6dB,-0dB. An input range from 0.5W to 60W (model dependent), and push-in connectors. Push-in connector allows quick terminal cable connection. Stylishly finished, the AT Series will suit any décor. |