The VX-2000DS Emergency Power Supply Unit supplies the DC power to each equipment in the VX-2000 system by connecting the VX-200PS Power Supply Unit. It keeps the battery unit that contains 2 × 12 V sealed lead batteries charged compensating for the temperature of the battery charging voltage. When the DC power supply from the VX-200PS stops, the VX-2000DS is automatically switched to the backup battery.
Power Source | 230 V AC | Power Consumption | 240 W max. | Applicable Battery | YUASA NP series (12 V × 2 or 4) | Charging Method | Trickle charging | Charging Current | 5 A max. | Charging Output Voltage | 27.3 V ±0.3 V (at 25℃)
Temperature correction coefficient: -40 mV/℃ | Power Supply Input | 6 M4 screw terminal | DC Power Output | 6 (25 A max. each) M4 screw terminal | Control Connector | RJ45 female connector for connecting the VX-2000SF Surveillance Frame.
Twisted-pair straight cable (TIA/EIA-568A standard)
Type of control signal: Battery check
charging circuit failure | Battery Connection | 1 pair of positive and negative terminals
Applicable cable diameter: AWG 6 - AWG 1/0 | Operating Temperature | 0℃ to +40℃ | Finish | Panel: Surface-treated steel plate | Dimensions | 482 (W) × 88.4 (H) × 377.6 (D) mm | Weight | 10.5 kg | Accessory | Rack mounting screw ……4
Fuse (T3.15 A L) ……1
Attention label (German) ……1 |
|
Emergency combination system. Ενσωματώνεται σε σύστημα συναγερμού φωτιάς. Ενσωματωμένο πυκνωτικό μικρόφωνο για Επείγουσα Αναγγελία, Εξωτερική αυτόματη αναγγελία με αρχείο φωνής, Επιλογέας δοκιμής. Ρύθμιση έντασης εξόδου, Βάρος 4,6kg. Διαστάσεις (WxHxD): 482X88X380mm |
- PRIORITY CONTROL It controls the priority of emergency, timer, remote1, remote2, main(normal). - AUTO FIRE SENSOR The fire alarm will be given automatically to the designated areas by detecting fire sensor input. - SPEAKER SWITCHING ON EMERGENCY OR NORMAL(MAIN) You can control the speaker relay on emergency or normal(main) mode by using the speaker switch on front panel. - DISPLAY STATUS You can easily check the priority status. - 2 AND 3 WIRE SPEAKER LINE SYSTEM You can control the speaker line on the 2 wire system or 3 wire system. - EXTENSION FUNCTION You can easily expand by connecting additional ECS-616.
ECS-616 | Priority Control | Emergency >Timer > Remote1 > Remote2 > Main | Link in/ out Interface | RS-422(19200bps,Data 8bits,Stop 1bit, Non Parity bit, Start1bit) | Link in/ out interface Distance | 1.2 km | Operation Temperature | -10 °C ~+ 40 °C | Power Source | 24V DC | Power Consumption | 900mA | Weight | 4.8Kg/10.6Ib | Dimensions( W x H x D) | 482(W)x 88(H) x 380(D) mm / 19(W)x 3.5(H)x 15(D)in | ※ Specifications and design subject to change without notice. |
|
| - SYSTEM POWER CONTROL You can control the power of your system by using this model. - AC AND DC POWER SUPPLY You can distribute AC and DC power through the AC outlet and DC terminals on the rear panel. - USE OF EMERGENCY POWER SUPPLY For emergency equipment power supply, an extra DC terminal is provided. - REMOTE CONTROL You can control the system power by remote control function even though the power switch on front is off. - AC AND DC VOLT METER This model uses digital volt meter displays of AC and DC. - OPERATING MODE DISPLAY You can easily check the operating mode by LEDs, AC or DC operating and emergency power. | | | | | PD-659 | AC Outlet | Switched 2000W ⅹ3 | Unswitched 700W ⅹ1 | Remote Control | 1 | DC Power Output | DC 24V 5A | Operation Temperature | -10℃~+40℃ | Power Source | 100-120VAC or 220-240VAC; 50/60Hz (Supplied ACmains transformer depends on country requirements) | Power Consumption | 190W | Weight(SET) | 6.2Kg/13.6Ib | Dimension(SET) | 482(W) x 88(H) x 380(D)mm/19(W) x 3.5(H) x 15(D)in | ※ Specifications and design subject to change without notice. | | | |
|
The ATT-30 from Inter-M Americas is a one-gang wall panel attenuator. The knob has four clearly-labeled steps to make easy adjustments. A screwless terminal block simplifies installation, and the sleek, modern design fits into any environment. The attenuator can handle up to 30W. |
Five attenuation settings (OFF, 0/-6/-12/ -16dB), over an input range from 0.5W to 30W. |