Content |
The VX-200SZ is an audio signal output module of the VX-2000 system with speaker line impedance detection. This module is to be mounted in the VX-2000SF Surveillance Frame and detects speaker line short circuits, open circuits by comparing impedance readings, and ground fault.
Power Source | Supplied from VX-2000SF | Current Consumption | Under 150 mA | Power Amplifier Link | RJ45 female connector for connecting the VP-2064, VP-2122, VP-2241,
VP-2421 Power Amplifier.
Twisted-pair straight cable (TIA/EIA-568A standard) | External Attenuator Control Output | Plug-in screw connector, relay, no-voltage make contact output,
transfer type, withstand voltage: 30 V DC, 250 V AC,
contact current: Under 7 A (DC), under 7 A (AC)
Applicable cable diameter: AWG 24 - AWG 16 | Speaker Output | Plug-in screw connector
Applicable cable diameter: AWG 24 - AWG 16 | Power Amplifier Input | Plug-in screw connector for connecting the VP-2064, VP-2122, VP-2241,
VP-2421 Power Amplifier.
Applicable cable diameter: AWG 24 - AWG 16 | Fault Detection System | Short circuit, open circuit (impedance detection method), ground fault | Finish | Panel: Surface-treated steel plate | Dimensions | 30.5 (W) × 132.6 (H) × 290.3 (D) mm | Weight | 320 g | Accessory | Plug-in screw terminal……1 | Option | Equaliser card: VX-200SE | Applicable Model | VX-2000SF |
|
The RM-300MF Fireman's Microphone is designed for exclusive use with the VM-3000 Series. It is equipped with an emergency activation key, permitting pre-recorded evacuation and alert announcements to be activated, and microphone announcement to be made in emergency situations. By connecting the RM-320F Fireman's Microphone Extension to the RM-300MF, the number of function keys can be expanded. The zone selection or failure acknowledgment function can be assigned to such function keys.
Power Source
|
24 V DC (operating range: 15 - 40 V DC, supplied from the VM-3000 system)
|
Current Consumption
|
120 mA (RM-300MF), 660 mA (with 3 RM-320F connected)
|
Frequency Response
|
200 Hz - 15 kHz
|
Distortion
|
1 % or less
|
S/N Ratio
|
55 dB or more
|
Microphone
|
Unidirectional dynamic microphone with talk key, compressor (on/off switchable)
|
Volume Control
|
Microphone volume control, Buzzer volume control
|
Connection Cable
|
Main line: Shield CPEV cable (each one pair of Audio line, Data line, Power supply line)
or Category 5 Shielded Twisted-Pair straight cable for LAN (CAT5-STP), M3 screw terminal
|
Maximum Cable Distance
|
Total 800 m (874.89 yd)
|
No. of Connectable RM-320F
|
Max. 3 units
|
Operation
|
Emergency key, Evacuate key, Alert key, Emergency reset key, CPU switch, Reset switch
|
Indicator
|
Power indicator, Emergency indicator, Communication failure indicator, CPU OFF indicator,
Evacuation announcement indicator, Alert announcement indicator,
Emergency reset indicator, Microphone in-use indicator,
Emergency broadcast equipment in-use indicator
|
Operating Temperature
|
-5 ℃ to +45 ℃ (23 ゜F to 113 ゜F)
|
Operating Humidity
|
5 % to 95 %RH (no condensation)
|
Finish
|
ABS resin, blueish gray (PANTONE 538 or its equivalent)
|
Dimensions
|
200 (W) × 215 (H) × 82.5 (D) mm (7.87" × 8.46" × 3.25“)
|
Weight
|
1.1 kg (2.43 lb) (with wall mounting bracket unit)
|
Accessory
|
Wall mounting bracket unit…1, Wall mounting screw…2
|
|
The JBL MTC-300T150 150 Watt Transformer is intended for use with 70V or 100V distributed loudspeaker lines. It is ideally suited for the Control Series 300, especially the 300BB12 Backbox which includes a preinstalled mounting location. |
| - FAN FOR PA RACK Auto fan operates when the inside temperature of PA RACK goes up. - MANUAL OPERATING When it's manual mode, the fan operates always regardless of temperature. - AUTO OPERATING When it's auto mode, the fan operates at 35°C. | | | | | PF- 602 | Operation Selector Switch | Manual, Auto, Operating temperature | Fan | 2 DC fans | Power Source | 24VDC | Power Consumption | 160mA | Weight | 4Kg/8.8Ib | Dimensions( W x H x D) | 482x 88 x 380 mm / 19 x 3.5 x 15in | ※ Specifications and design subject to change without notice. | | | |
|
toa-at-100upr Build-in Attenuator with Relay
Toa - 100V installation
Build-in Attenuator with Relay 100 W / 100 V
|
- PRIORITY CONTROL It controls the priority of emergency, timer, remote1, remote2, main(normal). - AUTO FIRE SENSOR The fire alarm will be given automatically to the designated areas by detecting fire sensor input. - SPEAKER SWITCHING ON EMERGENCY OR NORMAL(MAIN) You can control the speaker relay on emergency or normal(main) mode by using the speaker switch on front panel. - DISPLAY STATUS You can easily check the priority status. - 2 AND 3 WIRE SPEAKER LINE SYSTEM You can control the speaker line on the 2 wire system or 3 wire system. - EXTENSION FUNCTION You can easily expand by connecting additional ECS-616.
ECS-616 | Priority Control | Emergency >Timer > Remote1 > Remote2 > Main | Link in/ out Interface | RS-422(19200bps,Data 8bits,Stop 1bit, Non Parity bit, Start1bit) | Link in/ out interface Distance | 1.2 km | Operation Temperature | -10 °C ~+ 40 °C | Power Source | 24V DC | Power Consumption | 900mA | Weight | 4.8Kg/10.6Ib | Dimensions( W x H x D) | 482(W)x 88(H) x 380(D) mm / 19(W)x 3.5(H)x 15(D)in | ※ Specifications and design subject to change without notice. |
|