Content | A dedicated microphone for the VX-2000 system that fulfills the requirements of British and European standards:BS5839 part 8, EN60849 and IEC60849. The RM-200XF is designed to be exclusively used for emergency broadcast, however it can be used for general purpose broadcast applications as well.
Specification |
|
Power Requirement |
24V DC (Operating range: 16 - 40V DC) |
Current Consumption |
Under 200mA (RM-200XF), 850mA (with 10 RM-210s connected) |
Audio Output |
0db*, 600, balanced |
Hand-Held Microphone |
Dynamic microphone, Function switch (default: Press-talk), Microphone element fault detection |
Distortion |
Under 1% |
Frequency Response |
100 - 15,000Hz |
Signal-to-Noise Ratio |
Over 55dB |
Internal Speaker |
200mW |
Volume Control |
Microphone volume control, Monitor speaker volume control |
Number of Function Keys |
5 (including Hand-held micropnone's switch), extendable up to 105 (with 10 RM-210s connected)
Key Extension 10 keys extension per RM-210, EXTENSION connector |
Number of Connectable Units |
4 |
Communication System |
LONWORKS twisted pair free topology transceiver |
Connection Cable and Connector |
Category 5 STP cable, plug-in screw connector |
Communication Distance |
500m (Free topology wiring) |
Finish |
ABS resin, bluish gray (PANTON 538 or its equivalent) |
Dimensions |
200 (W) x 215 (H) x 82.5 (D)mm (excluding the coiled cord) |
Weight |
1.2kg |
Accessory |
Plug-in screw terminal x 1, Wall mounting bracket x 1, Wall mounting screw x 2, Box mounting screw x 2 |
Applicable Box |
YC-301, YC-11A |
|
*0 dB = 1 V |
|
| - SYSTEM POWER CONTROL It controls the power of the rack system over all working together with the PD-659. - AC OUTLET TERMINAL To make the units using AC work, it has an AC outlet terminal for your convenience. AC switched group turn on and off repeatedly every 2 seconds. | | | | | PD- 658 | AC Outlet | Switched 2000W ⅹ3 | Operation Temperature | -10℃~+40℃ | Power Source | 100-120VAC or 220-240VAC; 50/60Hz (Supplied AC mains transformer depends on country requirements) | Power Consumption | 10W | Weight(SET) | 4.6Kg/10.1 Ib | Dimension(SET) | 482(W) x 88(H) x 380(D)mm/19(W) x 3.5(H) x 15(D)in | | | |
|
The ATT-30 from Inter-M Americas is a one-gang wall panel attenuator. The knob has four clearly-labeled steps to make easy adjustments. A screwless terminal block simplifies installation, and the sleek, modern design fits into any environment. The attenuator can handle up to 30W. |
The RM-300MF Fireman's Microphone is designed for exclusive use with the VM-3000 Series. It is equipped with an emergency activation key, permitting pre-recorded evacuation and alert announcements to be activated, and microphone announcement to be made in emergency situations. By connecting the RM-320F Fireman's Microphone Extension to the RM-300MF, the number of function keys can be expanded. The zone selection or failure acknowledgment function can be assigned to such function keys.
Power Source | 24 V DC (operating range: 15 - 40 V DC, supplied from the VM-3000 system) | Current Consumption | 120 mA (RM-300MF), 660 mA (with 3 RM-320F connected) | Frequency Response | 200 Hz - 15 kHz | Distortion | 1 % or less | S/N Ratio | 55 dB or more | Microphone | Unidirectional dynamic microphone with talk key, compressor (on/off switchable) | Volume Control | Microphone volume control, Buzzer volume control | Connection Cable | Main line: Shield CPEV cable (each one pair of Audio line, Data line, Power supply line)
or Category 5 Shielded Twisted-Pair straight cable for LAN (CAT5-STP), M3 screw terminal | Maximum Cable Distance | Total 800 m (874.89 yd) | No. of Connectable RM-320F | Max. 3 units | Operation | Emergency key, Evacuate key, Alert key, Emergency reset key, CPU switch, Reset switch | Indicator | Power indicator, Emergency indicator, Communication failure indicator, CPU OFF indicator,
Evacuation announcement indicator, Alert announcement indicator,
Emergency reset indicator, Microphone in-use indicator,
Emergency broadcast equipment in-use indicator | Operating Temperature | -5 ℃ to +45 ℃ (23 ゜F to 113 ゜F) | Operating Humidity | 5 % to 95 %RH (no condensation) | Finish | ABS resin, blueish gray (PANTONE 538 or its equivalent) | Dimensions | 200 (W) × 215 (H) × 82.5 (D) mm (7.87" × 8.46" × 3.25“) | Weight | 1.1 kg (2.43 lb) (with wall mounting bracket unit) | Accessory | Wall mounting bracket unit …1, Wall mounting screw …2 |
|
The JBL MTC-300T150 150 Watt Transformer is intended for use with 70V or 100V distributed loudspeaker lines. It is ideally suited for the Control Series 300, especially the 300BB12 Backbox which includes a preinstalled mounting location. |